Multi-Channel TL-260 data logger with universal inputs is the perfect solutions for industrial and automation applications.
Features:
- Universal Analog Inputs
- High Performance
- High Accuracy
- 16/24 Bit Resolution
- Gain Selectable on Channels
- Data Record on Micro SD
- Programmable High and Low Alarms
- Real Time Data View in Software
- Alarm Display on LCD
The TL-260 data logger with universal inputs is the perfect solutions for industrial and automation applications.
Analog inputs are configurable to measure voltage,
current, Pt100 & Thermocouples, also digital channels can be used to detect pulse changes and frequency measurements.
Daloco software is used for data read out, device configuration, reading real time values and live charting.
8-Relay output channels are used for controlling peripherals in case of alarm on any input channels.
Measured signal values automatically convert to engineering units according to user configuration.
General Parameters:
Channel Numbers | 8-Analog input, 2-Digital input, 8-Relay output |
Analog Inputs | DC Current: 0~24 ma DC Voltage: Class A: 0~ 10 V Class B: 0~ 5 V PT100-Thermocouple |
Conversion Resolution | Class A: 24-Bit Class B: 16-Bit |
Digital Inputs | Pulse Max 20VDC Frequency up to 10Khz |
sampling rate | Class A: 100 Hz Class B: 4 Hz |
Power | 12 ~ 15 VDC |
Memory | Internal:16000 Records External micro SD up to 32GB |
Record Time Interval | Class A:10 mili seconds ~ 24 hours Class B:250 mili seconds ~ 24 hours (configured by software) |
PC Interface | USB-B Port |
Serial Interface | TL-270.10: – TL-270.11: RS485 Modbus TL-270.12: RS232 General TL-270.13: RS232 GSM Modem |
Working Temperature | -30 ~ 80°C Not for use in condensing conditions |
Dimensions | 157x99x45mm |
Voltage Characteristic
Input Ranges Single Ended: 0 ~ 5 VDC
unipolar/bipolar:
± 2.5VDC/Gain
For example Gain=128
Input Rage= ±19.53mVDC
Gain Select 1~128
Noise RMS 5.1 μV @ Gain=1
2.5 μV @ Gain=2
1.2 μV @ Gain=4
0.7 μV @ Gain=8~128
Resolution 0.1 mv @ 0 ~ 5 VDC
10 μV @ ± 2.5V
5 μV @ ± 1.25V
1 μV @ ± 300 mV
Accuracy 5 mV @ 0 ~ 5 VDC
100 μV @ ± 2.5V
50 μV @ ± 1.25V
10 μV @ ± 300 mV
Current Characteristic
Measure Range 0 ~ 25mA
Resolution 0.1 μA
Accuracy 3 μA
Input Impedance 100 Ω
RTD Characteristic
Probe Type PT100
2-3-4 wire connection
Resolution 0.01 °C
Accuracy Typical 0.5°C
Thermocouple Measuring Characteristic
Probe Type J,R,S,B,N,K,E,T
Resolution 0.1 °C
Typical Accuracy 0.5°C @ J,N,K,E,T
1.2°C @ R,S,B
Check more detail on the data sheet
Product No. | Details |
---|---|
ML-260.10.1 | Master Logg Universal Input Data Logger with RS232 Interface |
ML-260.10.2 | Master Logg Universal Input Data Logger with RS485 Interface |
MLC-08 | 8 channel Relay Controller for Master Logg Connects using RS485 Interface |